Normally closed 6 bar

 

 

1/2”….2” DN65 – DN80 – DN100

 

 

Solenoid valves are connected to a gas detector and shut off the gas flow when an alarm is detected.After alarm situation is removed, solenoid valve must be reset manually. In order to reset the valve,check that the coil is receiving current, for threaded models unscrew the protection cap and pull the reset knob. Screw the cap when operation is completed.For flanged models unscrew the protection cap and screw it down in the apposite threading and pull it up.When operation is completed,unscrew the cap and screw it in first position.

 

Technical specifications
 

Power supply : 230 Vac, 24 Vac , 12 Vdc
Body : ½” , ¾” , 1” , 1 ¼” , 1 ½” , 2” brass
DN65 ,DN80 ,DN100,DN125,DN150 aluminium
Maximum pressure : 6 bar   (2 bar for DN 125 and DN150 )
Closing time : ≤ 1sn.
Working temperature : -15°C…+70°C
Protection grade : IP 65
Threaded connection : ISO 228/1
Flanged connection : UNI 2223

 

 

 

 

Code Diameter Connections Dimensions (mm)
A B
23501/6 ½” Threaded  86 165
23501/6-12 ½” Threaded  86 165
23502/6 3/4" Threaded  86 165
23502/6-12 3/4" Threaded  86 165
23503/6 1" Threaded  93 175
23503/6-12 1" Threaded  93 175
23601/6 1 ¼” Threaded 114 200
23601/6-12 1 ¼” Threaded 114 200
23602/6 1 ½” Threaded 114 200
23602/6-12 1 ½” Threaded 114 200
23603/6 2” Threaded  138 210
23603/6-12 2" Threaded  138 210
23701/6 DN65 Flanged 246 395
23701/6-12 DN65 Flanged 246 395
23702/6 DN 80 Flanged 265 395
23702/6-12 DN80 Flanged 265 395
23703/6 DN100 Flanged 265 420
23703/6-12 DN100 Flanged 265 420