BP 2284

 

 

These low pressure regulators with OPSO safety valve are mainly dedicated to meter box installations.They can be used with Natural Gas,LPG (butane,propane and their mixture) or other non-aggressive gases (air,nitrogen,…).Regulator is equipped with double inlet and double outlet . The plug,factory fitted on one of these inlets and outlets,can be unscrewed and moved so as to achieve the desired geometry.

 

 

OPSO : OPSO safety stops the gas flow when the regulated pressure is higher than a defined value. Easy resetting : cap rotation allows pressure balancing before complete resetting. Visual indicator displays open-close state. Sealing wire (optional). It can be provided.
UPSO : UPSO safety stops the gas flow when the regulated pressure is lower than a defined value. Push button easy resetting,independent from OPSO resetting. Optional.
PRV : Pressure relief valve.Some models are equipped with a limited capacity pressure relief valve (LRV) which discharges thermal expansion over pressures and avoids any unnecessary OPSO triggering. Optional.
Vent : The vent can be connected to a pipe ( to be used when the regulator is installed in a not ventilated or safe area).
Test Point : a “hose” type test point allows controlling the regulated pressure. Optional.